Required:
Section 3.2.5
Shall > Indicates a mandatory
Section 3.2.6
Should > Indicates a Recommendation or Advised
Classifications of Fires:
5.2.1 Class A Fires
Class A fires are fires in ordinary combustible materials, such as wood, cloth, paper, rubber, and many plastics
5.2.2 Class B Fires
Class B fires are fires in flammable liquids, combustible liquids, petroleum greases, tars, oils, oil-based paints, solvents, lacquers, alcohols, and flammable gases
5.2.3 Class C Fires
Class C fires are fires that involve energized electrical equipment
5.2.4 Class D Fires
Class D fires are fires in combustible metals, such as magnesium, titanium, zirconium, sodium, lithium, and potassium
5.2.5 Class K Fires
Class K fires are fires in cooking appliances that involve combustible cooking media (vegetable or animals oils and fats)
Placement
Section 6.1.3.1
Shall be readily accessible and immediately available when a fire
Section 6.1.3.2
Shall be located along normal paths of travel, including exits
Visual Obstructions
Section 6.1.3.3.1
Shall not be obstructed or obscured from view
Cabinets
Section 6.1.3.11*
Shall not be exposed to temp. outside the listed temp. range
Installation Height
Section 6.1.3.8.1
Gross weight not exceeding 40lb (18.14kg), shall be installed not more than 5ft (1.53m) above the floor
Section 6.1.3.8.2
Gross weight greater than 40lb (18.14kg), (except wheeled types) shall be installed not more than 3.5ft (1.07m) above the floor
Section 6.1.3.8.1
Fire extinguisher bottom and floor shall be clearance 4 inches (102mm)
Travel Distance
Section 6.2
Can’t more than 30ft or 50ft based on the type of hazard
6.2.1.2.2 Class A Hazards
Shall not exceed 75ft (22.9m)
6.3.1.4 Class B Hazards
Shall not exceed 50ft (15.25m)
6.4.3 Class C Hazard
Shall not exceed 50ft (15.25m)
6.5.2 Class D Hazards
Shall not exceed 75ft (22.9m)
6.6.2 Class K Hazards
Shall not exceed 30ft (9.1m)
Inspection
Section 7.2.1
Visually inspected monthly at a minimum of 30 day
Section 7.2.4.1.1
The record shall be kept on a tag or label attached
Inspection Procedures
Section 7.2.2
Periodic or electronic monitoring shall check at least the following items:
- Location in a designated place
- No obstruction to access or visibility
- Indicator in range or position
- Determined by weighting or hefting
- Tires, wheels, carriage, hose, and nozzle good condition
- Non-rechargeable push-to-test
Maintenance
Section 7.3.4*
Annual Maintenance Record Keeping
Section 7.3.4.1.1
The tag or label, as a minimum, shall identify the following:
- Month and year maintenance was performed
- Person performing the work
- Name of the agency performing the work
Hydrostatic Testing
Hydrostatic test intervals for Extinguishers maximum of 5 years, following the chart